TD-65E

Diagnostic testing for cables rated to 35kV

Interested
in the ?

Specifications

Input:Two Alkaline “D” cell batteries required – Four supplied
rechargeable “D” cell batteries acceptable – Not included
Metering:Voltage: 1-65kVp(46kVrms), ±1% Accuracy, 0.1kV Resolution
Current: 0-150mAp(106mArms), ±1% Accuracy, 1uA Resolution
Tan Delta: 0.1Hz -0.01Hz, 5nF-10uF, 1.0 x 10-₄ Accuracy, 1.0 x
10-₅ Resolution
PC Interface:XBee 802.15.4 (wireless, ~30ft range)
PC Software:E-Link remote control and report generation software
Interconnect Cables:88-5061 – 20ft/6.1m VLF output cable for use with VLF-34E
81-5520 – 20ft/6.1m VLF output cable for use with VLF-65E S/N 1000-1285
88-514 – 20ft/6.1m output cable for use with VLF-65E S/N 1286 & higher
(Sold Separately)
Included Cables:10ft/3m TD output lead terminated with red banana clip,
20ft/6.1m green/yellow test lead, 2in/51mm x 5in/127mm
toroid, 1 1/2in/38mm aluminum ball with banana socket
Size:TD Transducer w/ Tripod: 7in/152mm x 8in/203mm x
18in/457mm TD Carrying Case: 22.5in/572mm x 15in/381mm
x 11.75in/298mm

Condition Assessment Criteria

*All numerals are 10-₃ per Section 5, Tables 4 & 5 of IEEE 400.2-2013

 

Conditional AssesmentNo Action RequiredFurther Study AdvisedAction RequiredNo Action RequiredFurther Study AdvisedAction RequiredNo Action RequiredFurther Study AdvisedAction Required
Insulation TypePE Based Insulation (PE, XLPE, WTRXLPE)Unidentified Filled Insulation (EPR)Mineral Filled Insulation (EPR)
Stability for TD Standard Deviation)< 0.050.05 to 0.5> 0.5> 0.10.1 tо 1.3> 1.3< 0.10.1 to 1> 1
AndOrAndOrAndOr
Tip Up (TD1.5U0 – TD0.5U0)< 550 to 80> 80> 55 tо 100> 100< 44 to 120> 120
AndOrAndOrAndOr
Mean TD @ UO< 44 to 50> 50> 3535 tо 120> 120< 2020 to 100> 100