VLF-140CMF

High Voltage VLF Hipot with Cable Burn Mode

Interested
in the ?

Features and Benefits

The High Voltage, Inc. VLF-140CMF was designed for withstand and diagnostic testing of cable systems up to 110kV. The VLF-140CMF is a higher power alternative to our VLF-12011CMF, capable of testing up to 70,000 feet (21km) of cable. It can be used as a voltage source for tan delta or partial discharge equipment for cable diagnostics. HVI introduced our patented sinewave output VLF technology in 1997 and the VLF-140CMF has been manufactured since 2012. The multi-piece design allows many transportation configurations, cargo trailer, flatbed, custom designs.

The VL-140CMF comes standard with our ADL-2. The ADL-2 module and its software are designed to log VLF test voltages and currents and conveniently generate test reports. The ADL-2 module embedded in the VLF transmits the voltage and current data to the software via an Xbee 802.15.4 wireless link and the software stores the values and displays them on a graph vs. time as well as numerically. The software also calculates VLF frequency and capacitance of the test load.

Specifications

Input: 230 V single phase, 80 A peak, 50/60 Hz
Output: 0-140 kV AC peak, 100 mA (bushing output – cable not included)
Duty: Continuous
Load Rating: 1.5 µF @ 0.1 Hz
3.0 µF @ 0.05 Hz
7.5 µF @ 0.02 Hz
Voltmeter: 0 – 140 kV AC peak, 3.5″ analog display
Charging Current Meter: 0 – 200 mA, 3.5″ analog display
Dual Range Load Capacitance Meter: 0-6/0-60 µF The CAPACITANCE scale is for measuring the load cable capacitance (0- 6uF/0-60uF) prior to test to determine the best operating frequency
Size & Weight:
(W x D x H)
Controls
24 x 30 x 62 in., 750 lb.
610 x 762 x 1575 mm, 2341kg
HV Tank:
60 x 37 x 62h in., 2650 lb.
1524 x 940 x 1575hmm, 1161 kg

Request a Quote