PFT-302CE

Portable AC Hipot for Apparatus Testing

The PFT-302CE AC hipot test set provides continuously adjustable output voltages for overvoltage withstand testing of the following:

  • Switchgear
  • Circuit breakers
  • Reclosers
  • Vacuum bottles
  • Hot sticks
  • Motor windings
  • Other high voltage insulation requiring AC

Features:

  • Continuously adjustable output voltage
  • Adjustable overload, 10-110% of rated output current
  • Primary backup circuit breaker
  • Zero start and external interlock provision
  • Secondary connected single-range digital voltmeter with memory at overload
  • Single-range digital current meter with guard/ground return circuit
  • Shielded output cable precludes unnecessary insulated support of the cable
  • One-piece portable design
Input: 230 V, 15 A, 50/60 Hz, single phase
Output: 0 – 30 kV AC, up to 67 mA depending on load, sinusoidal
Duty: 2 kVA—1 hour ON, 1 hour OFF
1 kVA—Continuous
Distortion: Less than 5%
Meter Accuracy: 1%
Voltmeter: 3.5” digital LED, scaled 0-30.0 kV AC (RMS)
Current Meter: 3.5” digital LED, scaled 0-67.0 mA
Size & Weight:
(W x D x H)
23 x 11.5 x 15.5 in., 77 lb.
585 x 293 x 395 mm, 35 kg
Output Termination: 20 ft. long shielded cable




REQUEST A QUOTE